Project Name: C21-1153 Project Description: EPLANS- CANDLEWOOD SUITES/HOLIDAY INN EXPRESS Review Comments List Date: 9/30/2021
Ref. # 160, 8/17/21 3:50 PM, Cycle 3, Unresolved
Markup: Struc 38, S3.0B.pdf
It is not clear how the roof framing members are supported at the corner overhang; please provide framing connections or hangers.
Reviewer Response: 9/30/21 1:58 PMThe roof framing remains unclear as to how it is to be constructed, Please provide adequate construction plans, connection details and the calculations for this entry roof. The roof remains with unsupported roof corners at the large overhangs.
Ref. # 161, 8/17/21 3:55 PM, Cycle 3, Unresolved
Markup: Struc 37, S3.0A.pdf
Please clarify the force transfer around diaphragm openings mechanism per the requirements of ASCE 7.
Reviewer Response: 9/30/21 2:19 PMThe lack of plan irregularity does not waive the transfer of shear forces around the openings by the principles of engineering mechanics, similar to openings in shear walls, utilizing tension and compression collector members. Diaphragm calculations were not found in the calculation package; please provide.
Ref. # 164, 8/17/21 4:04 PM, Cycle 3, Unresolved
Markup: Struc 41, S8.1.pdf
Please provide a connection to brace the wall for out-of-plane forces.
Reviewer Response: 9/30/21 2:32 PMPlease provide members, straps or connectors to transfer the out-of-plane wind and seismic wall forces into the diaphragm at all parallel joist conditions as required by AWC SDPWS 4.2.1. Blocking and connections are not currently shown.
Ref. # 170, 8/31/21 9:58 AM, Cycle 4, Unresolved
Comment: Please provide structural construction drawings for the pool and spa areas that are sealed by an engineer registered in the State of Alaska. Please reference the "SP" drawings.
Reviewer Response: 9/30/21 1:54 PMDeferred submittal items shall be listed on the construction documents by the design professional in responsible charge in accordance with IBC 107.3.4.1. Please provide.
Ref. # 190, 9/30/21 12:47 PM, Cycle 5, Unresolved
Markup: Struc 43, S2.0B.pdf
The calculations call out HSS6x6x1/4 columns; please revise.
Ref. # 199, 9/30/21 2:40 PM, Cycle 5, Unresolved
Comment: Please reload all structural drawings in ePlans with clean, un-editable PDF files. The drawings currently contain text attributes that are incompatible with the ePlans system.