Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C21-1153
Permit Type: Commercial Building Permit - None BldgNew
Address: W 160 48TH AVE Anchorage
Location: 160 W 48th Ave
Work Description: EPLANS-117094 SQFT, TYPE VB, OCCUPANCY R-1-GJS
NO CCO ON THIS PERMIT UNTIL SHARED ACCESS WITH C15-1806 IS RESOLVED. JCA 6/19/23 Resolved with change order X22-1625. JCA 8/13/24

**REVOKED MAIN PERMIT AND ISSUED CORE AND SHELL ONLY PER JUDY 6/19/23 - SEE HER COMMENTS UNDER PD CIVIL REVIEW - BWP**
Change order X22-1625 has been approved and this permit (C21-1153) has full PD Civil approval.  - RDO (Per PDCivil Final Review)
***PHIL CALHOUN OKAYED A SATURDAY INSPECTION FOR 8/3/24 FOR INSUL/VAPOR BARRIER; PAID $800 FOR SATURDAY INSPECTION*** CCK 8/2/24
***JESSE SOOTER OKAYED SATURDAY INSPECTION FOR 11/23/24 FOR SHEETROCK SCREW PATTERN FOR 4TH FLOOR- CCK 11/22/24
Status: Issued
Project Name: EPLANS- CANDLEWOOD SUITES/HOLIDAY INN EXPRESS
Review Type: Plumbing
Result: Correction
Result Date: 8/12/2021 2:32:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

131
3
Plumbing
Leigh Bergstrom
8/12/21 11:23 AM
Changemark
PLUM-1
ELEVATORS SUMP PUMPS SERVING 4 OR MORE STORIES ABOVE GRADE SHALL HAVE THE CAPACITY TO REMOVE A MINIMUM OF 50 GALLONS PER MINUTE PER COMMON ELEVATOR HOISTWAY. IN ADDITION, HYDRAULIC ELEVATOR PIT DRAINAGE SHALL PASS THROUGH AN OIL/WATER SEPARATOR, OR OTHER APPROVED MEANS SHALL BE EMPLOYED TO PREVENT THE DISCHARGE OF HYDRAULIC FLUID. (LOCAL AMENDMENT 23.75.2.2.2) PLEASE CLARIFY.
M1.2.pdf
 
Unresolved
132
3
Plumbing
Leigh Bergstrom
8/12/21 11:29 AM
Changemark
PLUM-BERG
PUBLIC USE LAVATORIES (LAV-2 & LAV-5) REQUIRE AN ASSE 1070 POINT OF USE MIXING VALVE PER UPC 407.3. PLEASE CLARIFY.
M1.0.pdf
 
Unresolved
133
3
Plumbing
Leigh Bergstrom
8/12/21 12:00 PM
Changemark
PLUM-1
SHEET NOTE #2 AT "SALES 100-10" REFERS TO 4" RD UP. WOULDN'T THE HORIZONTAL PORTION OF THAT BRANCH ALSO BE 4"?
M2.2.pdf
 
Unresolved
134
3
Plumbing
Leigh Bergstrom
8/12/21 12:00 PM
Changemark
PLUM-2
REFERENCE SHEET NOTE #6, WE DID NOT FIND THE POOL SHOP DRAWINGS. PLEASE ADDRESS.
M2.2.pdf
 
Unresolved
135
3
Plumbing
Leigh Bergstrom
8/12/21 12:28 PM
Changemark
PLUM-1
2016 NFPA 13-10.4.3.1 LIMITS THE AMOUNT OF UNDERGROUND BUILDING SERVICE SPRINKLER PIPING TO A MAXIMUM OF 10 FEET.
M2.3.pdf
 
Unresolved
136
3
Plumbing
Leigh Bergstrom
8/12/21 12:28 PM
Changemark
PLUM-2
THE WATER SERVICE ENTRY DETAIL ON M2.8 SHOWS A 4" REDUCED PRESSURE BACKFLOW PREVENTER ON THE DOMESTIC WATER SERVICE TO THE BUILDING. PER LOCAL AMENDMENT TO UPC 603.4.8 A 6" AREA DRAIN WILL BE REQUIRED. THE 4" FD-2 AND SUBSEQUENT PIPING ARE NOT SUFFICIENT.
M2.3.pdf
 
Unresolved
137
3
Plumbing
Leigh Bergstrom
8/12/21 12:34 PM
Changemark
PLUM-3
A DIRECT CONNECTED FLOOR DRAIN IN PANTRY STORAGE 100.9 IS NOT PERMITTED PER UPC 418.4.
M2.2.pdf
 
Unresolved
138
3
Plumbing
Leigh Bergstrom
8/12/21 12:38 PM
Changemark
PLUM-1
PLEASE CLARIFY SHEET NOTES #1 THRU #4.
M2.4.pdf
 
Unresolved
139
3
Plumbing
Leigh Bergstrom
8/12/21 1:00 PM
Changemark
PLUM-1
FOR BUILDINGS WITH WATER SERVICE MORE THAN 30 FEET ABOVE GRADE, ONLY A DOUBLE CHECK VALVE IS REQUIRED PER LOCAL AMENDMENT TO UPC 603.5.26. AN RP DEVICE IS NOT REQUIRED.
M2.8.pdf
 
Unresolved
140
3
Plumbing
Leigh Bergstrom
8/12/21 1:00 PM
Changemark
PLUM-2
ELEVATOR SUMP PUMP PIPING OUTLETS ARE REQUIRED TO BE PERMANENTLY LABELED "ELEVATOR PIT DISCHARGE" PER LOCAL AMENDMENT 23.75.2.2.2.11. PLEASE CLARIFY.
M2.8.pdf
 
Unresolved
141
3
Plumbing
Leigh Bergstrom
8/12/21 1:00 PM
Changemark
PLUM-3
IT IS EVIDENT THAT THERE IS A DOMESTIC HOT WATER RECIRCULATION SYSTEM WITH THE INSTALLATION OF PUMP #HWC-103. PLEASE PROVIDE THE SYSTEM PIPING DETAILS ON THE OTHER APPROPRIATE PAGES.
M2.8.pdf
 
Unresolved
142
3
Plumbing
Leigh Bergstrom
8/12/21 1:11 PM
Changemark
PLUM-1
SUDS RELIEF PER UPC 711 WILL BE REQUIRED FOR THE RISERS CONNECTED TO TUBS, SHOWERS, DISWASHERS AND KITCHEN SINKS. PLEASE CLARIFY.
M2.9.pdf
 
Unresolved
143
3
Plumbing
Leigh Bergstrom
8/12/21 2:30 PM
Changemark
PLUM-1
FOR THE COPPER DOMESTIC WATER MAINS ON M2.0 & M2.1 PLEASE CLARIFY THE MEANS OF EXPANSION COMPENSATION.
M2.0.pdf
 
Unresolved

156
3
Plumbing
Leigh Bergstrom
8/13/21 8:52 AM
Comment
PROVIDE A GAS PIPING SCHEMATIC DIAGRAM TO INCLUDE PIPE SIZES, ALL APPLIANCE INPUT LOADS, GAS PRESSURE AND LONGEST DISTANCE TO THE MOST REMOTE APPLIANCE SUCH THAT APPOPRIATE PIPE SIZES MAY BE DETERMINED.
  
Unresolved

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS