Permit Number: C21-1153
Permit Type: Commercial Building Permit - None BldgNew
Address: W 160 48TH AVE Anchorage
Location: 160 W 48th Ave
Work Description: EPLANS-117094 SQFT, TYPE VB, OCCUPANCY R-1-GJS
NO CCO ON THIS PERMIT UNTIL SHARED ACCESS WITH C15-1806 IS RESOLVED. JCA 6/19/23 Resolved with change order X22-1625. JCA 8/13/24

**REVOKED MAIN PERMIT AND ISSUED CORE AND SHELL ONLY PER JUDY 6/19/23 - SEE HER COMMENTS UNDER PD CIVIL REVIEW - BWP**
Change order X22-1625 has been approved and this permit (C21-1153) has full PD Civil approval.  - RDO (Per PDCivil Final Review)
CONTRACTOR TRANSFER FORM [FROM ACSC BUILDER TO MAD-AK] ON 6-8-2026 - RLH
Status: Issued
Project Name: EPLANS- CANDLEWOOD SUITES/HOLIDAY INN EXPRESS
Review Type: Electrical
Result: Approved
Result Date: 3/4/2021 8:58:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

The electrical plans are provided and reviewed and approved.

----------------------------------------------------------------------------------------------------------

Electrical Comments

 

Reviewed by: David Abuobaid                                                 Permit #: C21-1153

Phone:  343-8333                                                                     Date: 08/02/2021

Fax:      249-7775                                                                     

Email:   AbuobaidDH@muni.org

Permit  Manager: Brant Bennett

Phone:  343-8338

Email:   brant.bennett@muni.org

Project: Candlewood suites/Holiday Inn Express (fax: no fax provided)

____________________________________________________________________________________  

REQUIREMENT OF ELECTRICAL WORK:

The electrical plan sheets are not stamped and signed by a licensed engineer from the State of Alaska.

Please provide 100% designed engineered drawing by a registered professional electrical engineer of the State of Alaska. The design shall include existing service load calculations, panel schedules with connected, demand loads and amperage interrupting ampacity, home run wiring with size of wires and conduit on the one-line diagram.