78,062 sq ft (4) story mixed occupancy hotel OK TO ISSUE GRADING/EXCAVATION WITHOUT FEES PAID PER GRETCHEN 9/1/2017 PLAN REVIEW FEES PAID IN FULL, X17-1099 PAID IN FULL 6/6/18 ***10/9/18 OKAY FOR GENERAL TO P/U FOR JM MECH... SLO
***OK FOR F&F AND CORE/SHELL ONLY! - CHANGE ORDER REQUIRED FOR UPDATED CIVIL PLANS TO INLCUDE SHARED ACCESS (REF PERMIT #C21-1153) PRIOR TO ISSUING FULL PERMIT - RDO / G.SOULE 03/18/24***
*** ORIGINAL FEES WERE PAID BY CHECK WRITTEN BY PROPERTY OWNERS (ANCHORAGE MC HOLDING LLC). WRITTEN LETTER BY OWNER REQUIRED FOR EACH CONTRACTOR TRASNFER (ALL DISCIPLINES AS NECESSARY) - RED 6/26/24
MOA & MC HOLDING LLC AGREEMENT OF REINSPECTION FEES DUE (169 INSPECTIONS @$175/EA LOADED IN INFOR 7/2/24) TO PROCEED WITH PROJECT (EMAIL ATTACHED FOR RECORDS ALONG WITH TRANSFER OF CONTRACTORS TO JANSEN AS GENERAL AND SAMSON FOR ELECTRICAL)- RED 7/2/24
FULL PERMIT ISSUED - 9/3/24 - RED
4/15/16 Submittal;
1)Comment Addressed 5/5/16 ~ DB
2) Comment Addressed 2/18/16 ~ DB
3) Provide complete haul route information indicating routes meet the requirements of AMC 9.46.410. ~Comment remains ~ 5/5/16~ DB The haul route to the site is restricted to: site to International via A Street or Site to C Street via 48th Ave and A Street. Travel on any roadways north of 48th Ave and east of A Street is prohibited by the cited code. Modify the note as required to provide clear direction to the contractor.
4) Provide all signing and striping information on the Plot Plan / Civil sheets including striping call outs and pertinent installation details.~Comment remains ~ 5/5/16~ DB~ The signing and striping, details, and notes are shown on a mix of Civil and Architectural sheets. All information is required to be complete in one section of the plans whether on the Civil or Architectural. Parking space markings shall be clearly shown as 4" white and dimensioned for width and depth to include drive aisle widths. Provide specific details for the signing and marking of Loading Berths. Provide specific details for the required ADA signing and marking to include providing blue markings for access aisles. Parking space markings shall be 4" white with a supplemental 4" blue marking located inside the white marking for ADA spaces. Utilize the international ADA symbol provide in the MUTCD Figure 3B-22. Provide no parking signage in front of the 8' van accessible asile.
5) Comment Addressed 5/5/19 ~DB
6) Comment Addressed 2/18/16 ~ DB
7) Comment Addressed 2/18/16 ~ DB
8) Comment Addressed 2/18/16 ~ DB
9) Comment Addressed 5/5/19 ~DB
10) Comment Addressed 2/18/16 ~ DB.
11) Provide a certified Lighting and Glare statement indicating the lighting is designed and meets the requirements of AMC 21.45.080X4e (Old Code as the lighting section in new code is not complete). ~5/5/16~ DB ~ Comment remains. I could not find a revised sheet E1.4 referenced in the response to comment. Lighting and glare certifications are typically placed on the over all site plan or photometric sheet but is required.
12) Comment Addressed 5/5/19 ~DB
13) Fire lane signs shall face traffic and be mounted at 90 degrees to the curb. Provide back to back mounting in areas that they are mounted on one side of a drive aisle. Comment remains ~ 5/5/16. If the signing and striping is to remain on the A050 modify as required.
14) The plan set includes multiple details related to ADA which appear to conflict with each other. Specifically the ramp and curb cut details presented in G015 do not appear to be similar to those presented on Sheet A015 or Sheet C3.0.
15) Please verify that the building entrance at the west end is fully ADA compliant. AMC 21.07.090 J requires the ADA parking to be on the shortest most direct route to an accessible entrance.
~~Traffic review shall be considered incomplete pending submittal of further design information; additional comment may be generated. ~ 5/5/16 ~ DB