Permit Type: Commercial Building Permit - None BldgNew
Address: 4960 A ST Anchorage
Location: 4960 A ST
Work Description:

78,062 sq ft (4) story mixed occupancy hotel  OK TO ISSUE GRADING/EXCAVATION WITHOUT FEES PAID PER GRETCHEN 9/1/2017 PLAN REVIEW FEES PAID IN FULL, X17-1099 PAID IN FULL 6/6/18 ***10/9/18 OKAY FOR GENERAL TO P/U FOR JM MECH... SLO

***OK FOR F&F AND CORE/SHELL ONLY! - CHANGE ORDER REQUIRED FOR UPDATED CIVIL PLANS TO INLCUDE SHARED ACCESS (REF PERMIT #C21-1153) PRIOR TO ISSUING FULL PERMIT - RDO / G.SOULE 03/18/24***

*** ORIGINAL FEES WERE PAID BY CHECK WRITTEN BY PROPERTY OWNERS (ANCHORAGE MC HOLDING LLC). WRITTEN LETTER BY OWNER REQUIRED FOR EACH CONTRACTOR TRASNFER (ALL DISCIPLINES AS NECESSARY) - RED 6/26/24

MOA & MC HOLDING LLC AGREEMENT OF REINSPECTION FEES DUE (169 INSPECTIONS @$175/EA LOADED IN INFOR 7/2/24) TO PROCEED WITH PROJECT (EMAIL ATTACHED FOR RECORDS ALONG WITH TRANSFER OF CONTRACTORS TO JANSEN AS GENERAL AND SAMSON FOR ELECTRICAL)- RED 7/2/24

FULL PERMIT ISSUED - 9/3/24 - RED

Status: Issued
Project Name: COURTYARD BY MARRIOTT
Review Type: Traffic Engineering
Result: Correction
Result Date: 2/18/2016 11:34:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

2/5/16  Submittal;


1) Provide a copy of the CP&D Approved Site Plan. ~Comment remains ~ 2/18/16~ DB

2) Comment Addressed 2/18/16 ~ DB

3) Provide complete haul route information indicating routes meet the requirements of AMC 9.46.410. ~Comment remains ~ 2/18/16~ DB

4) Provide all signing and striping information on the Plot Plan / Civil sheets including striping call outs and pertinent installation details.~Comment remains ~ 2/18/16~ DB Parking space markings shall be white, ADA parking spaces may supplement the white markings with blue per MUTCD 3B.19. All signing and striping shall be indicated on the civil plans. Please include a sign schedule or other means to identify appropriate sign  codes and sizes.

5) Civil Sheets; Provide spot elevation information or other means to ensure constructability of all ADA accessibility requirements, including but not limited to ADA parking areas, access aisles, ramps, sidewalks and accessible loading facilities for slope and cross  slopes. Slope max call outs are acceptable. ~Comment remains ~ 2/18/16~ DB ~ All site accessibility requirements  per IBC 1104 and ICC A117.1 shall be provided for and indicated on the plans.

5a) There is nothing to indicate the parking and access aisles are 2 % maximum in any direction on Sheets C1.0 through C1.4  

5b) The cross sections on sheet C1.6 do not indicate 2% maximum for the sidewalks.

5c) Detail 2/C1.6 indicates a minimum 2% cross slope rather then the required Maximum Slope.

5d) Detail 2/C3.0 does not provide any slope or cross slope information.

5e) Sheet C1.2 indicates a cross slope of 6.6% between points 67 and 68. The rise over run between points 68 and 191 equate to a 2.2' difference and result in a running slope exceeding 5%. Provide required landings as well and handrails.

6) Comment Addressed 2/18/16 ~ DB

7) Comment Addressed 2/18/16 ~ DB

8) Comment Addressed 2/18/16 ~ DB


9) Sheet C1.0; Provide complete design information on the civil sheets. Please clarify how accessibility is being addressed at the pedestrian access route to A Street ~Comment remains ~ 2/18/16~ DB~ See Comment 5

10) Comment Addressed 2/18/16 ~ DB.

11) Provide a certified Lighting and Glare statement indicating the lighting is designed and meets the requirements of AMC 21.45.080X4e (Old Code as the lighting section in new code is not complete). ~ 2/18/16 ~ DB ~ Comment partially addressed. Provide the certified lighting and glare statement on the Electrical sight plan.


12) Up date the plot plan. The loading berth locations do not match the other civil sheets or the A050. The plat has recorded and the notes referencing the S# and preliminary plats require modification.


13) Fire lane signs shall face traffic and be mounted at 90 degrees to the curb. Provide back to back mounting in areas that they are mounted on one side of a drive aisle.

~~Traffic review shall be considered incomplete pending submittal of further design information; additional comment may be generated. ~ 2/18/16 ~ DB