Permit Number: C15-1806
Permit Type: Commercial Building Permit - None BldgNew
Address: 4960 A ST Anchorage
Location: 4960 A ST
Work Description:

78,062 sq ft (4) story mixed occupancy hotel  OK TO ISSUE GRADING/EXCAVATION WITHOUT FEES PAID PER GRETCHEN 9/1/2017 PLAN REVIEW FEES PAID IN FULL, X17-1099 PAID IN FULL 6/6/18 ***10/9/18 OKAY FOR GENERAL TO P/U FOR JM MECH... SLO

***OK FOR F&F AND CORE/SHELL ONLY! - CHANGE ORDER REQUIRED FOR UPDATED CIVIL PLANS TO INLCUDE SHARED ACCESS (REF PERMIT #C21-1153) PRIOR TO ISSUING FULL PERMIT - RDO / G.SOULE 03/18/24***

*** ORIGINAL FEES WERE PAID BY CHECK WRITTEN BY PROPERTY OWNERS (ANCHORAGE MC HOLDING LLC). WRITTEN LETTER BY OWNER REQUIRED FOR EACH CONTRACTOR TRASNFER (ALL DISCIPLINES AS NECESSARY) - RED 6/26/24

MOA & MC HOLDING LLC AGREEMENT OF REINSPECTION FEES DUE (169 INSPECTIONS @$175/EA LOADED IN INFOR 7/2/24) TO PROCEED WITH PROJECT (EMAIL ATTACHED FOR RECORDS ALONG WITH TRANSFER OF CONTRACTORS TO JANSEN AS GENERAL AND SAMSON FOR ELECTRICAL)- RED 7/2/24

FULL PERMIT ISSUED - 9/3/24 - RED

Status: Issued
Project Name: COURTYARD BY MARRIOTT
Review Type: Architectural
Result: FandF
Result Date: 10/23/2015 4:00:00 PM

Comments:

 Code SectionReview CommentStatus
1_
Drawing No. G001, Applicable Codes; Revise: International Plumbing Code (IPC)  2009 Edition to Uniform Plumbing Code (UPC) 2009 Edition.

2_
Drawing No. G001, Applicable Codes; Revise: National Electric Code (NEC) 2009 Edition to National Electric Code (NEC) 2011 Edition. Note: There is no National Electric Code (NEC) 2009 Edition.

3_
Drawing No. G001, Applicable Codes; Add to Applicable Codes: Accessibility Code:   Accessible and Useable Buildings and Facilities (ICC/ANSI A117.1) 2003.

4_
Drawing A020, Code Analysis; There is an error in the "Area Determination (IBC 506.4)" calculation.  The multiplier is shown as 4; however, it should be shown as 3 per IBC 506.4, item 2.  Note that exception 2 does not apply here because it is specifically for buildings with sprinklers in accordance with NFPA 13R (IBC Section 903.3.1.2) and not for buildings with sprinklers in accordance with NFPA 13 (IBC Section 903.3.1.1) which already gets a 200% area increase.

5_
Drawing A020, Code Analysis; There is an error in the "Actual Building Area by Floor" calculation.  Since you are using separated occupancies be IBC Section 508.4; the 45,000 denominator number is incorrect (it applies to R-1 occupancy).  What is required here is the similarly calculated denominator number for the the B, A-2, & A-3 occupancies.

6_
Drawing G004, Wall Details; Please show the continuity of the fire-resistive assemblies. The Vertical 2 hour assemblies do not seem to show continuity for details K and J (and possibly others)




Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C15-1806

Phone: 343-8451                                                                        Date: 10/12/15

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: COURTYARD BY MARRIOTT - 4960 A ST

Review Number: 359440

 

 