| Date | Status | Code | Description | Ref | Location | Comments |
| 7/2/2026 | Transfer | Correct Below | * | | (3) engineering changes from inspection #903878 that did not carry through to this inspection. | Changes involved: 1. Available fault current table. 2. 50A elevator circuits. 3. Dishwasher / disposal circuit changes. Submit to MOA Plan Review for approval. |
| 6/30/2026 | Corrected | Correct Below | * | | To extend conditional electrical final to gazebo. | Conditional electrical finals can only by issued for completed phased areas. The gazebo is part of Phase 4. Phase 4 is the gazebo and pool. Disconnect / lock-out the waterfall low voltage light until a permanent resolution of issues can be achieved. UPDATE: WATEWRFALL LOW VOLTAGE LIGHT POWER SUPPLY REMOVED AS A TEMPORARY SOLUTION. OWNER / CONTRACTOR WILL NEED TO DETERMINE A PERMANENT SOLUTION. |
| 6/30/2026 | Corrected | Correct Below | * | | Rooftop. | 2 out of 3 units not listed. UPDATE: CSA HAS PERFORMED A FIELD INVESTIGATION AND LABELLED THE UNITS IN QUESTION. |
| 6/30/2026 | Corrected | Correct Below | * | | 3RD floor heat trace breakers. | Breaker locking devices installed do not meet the requirements of 110.25. NOTE: 426.50(A) requires that disconnecting means is capable of being locked in the open position. |
| 6/30/2026 | Transfer | Correct Below | * | | Pool area low voltage "waterfall" light. | Low voltage lighting within 5ft of pool is required to conform to 680.22(B)(6). Specific low voltage power source requirements are at 680.23(A)(2). UPDATE: RECEIVED "BRILLIANT WONDERS" POOL WATERFALL LIGHT PRODUCT INFORMATION. POWER SUPPLY INSTALLED DOES NOT CONFORM TO THE NEC SECTION ABOVE. ETL LISTING REP FOR THE COMPANY NEEDS TO CONTACT INSPECTOR. |