| Date | Status | Code | Description | Ref | Location | Comments |
| 6/30/2026 | Transfer | Correct Below | * | | To extend conditional electrical final to gazebo. | Conditional electrical finals can only by issued for completed phased areas. The gazebo is part of Phase 4. Phase 4 is the gazebo and pool. Disconnect / lock-out the waterfall low voltage light until a permanent resolution of issues can be achieved. |
| 6/30/2026 | Transfer | Correct Below | * | | Rooftop. | 2 out of 3 units not listed. |
| 6/30/2026 | Transfer | Correct Below | * | | 3RD floor heat trace breakers. | Breaker locking devices installed do not meet the requirements of 110.25. NOTE: 426.50(A) requires that disconnecting means is capable of being locked in the open position. |
| 6/30/2026 | Transfer | Correct Below | * | | Pool area low voltage "waterfall" light. | Low voltage lighting within 5ft of pool is required to conform to 680.22(B)(6). Specific low voltage power source requirements are at 680.23(A)(2). UPDATE: RECEIVED "BRILLIANT WONDERS" POOL WATERFALL LIGHT PRODUCT INFORMATION. POWER SUPPLY INSTALLED DOES NOT CONFORM TO THE NEC SECTION ABOVE. ETL LISTING REP FOR THE COMPANY NEEDS TO CONTACT INSPECTOR. |
| 5/29/2026 | Transfer | Correct Below | * | | All units with dishwashers and disposals. | Field installation has both appliances on the same circuit. Verify that engineer has submitted change order to MOA Plan Review. |
| 5/29/2026 | Transfer | Correct Below | * | | 50A elevator circuits. | 1-line drawing shows (4) 50A elevator circuits supplied directly from MDP. Installation varies from 1-line drawing. Requires change order submitted to MOA Plan Review to show: 1. Coordination study between 200A feeder OCPD and 50A elevator circuit OCPDs. 2. 1-line changed to show 50A elevator circuits supplied from 200A elevator panels as installed. 3. Recalculated available fault current. |
| 5/29/2026 | Transfer | Correct Below | * | | Available fault current table on drawings. | Various panels show less than 10K available fault current. Table shows 22K equipment rating. Change table to allow 10K breakers and submit to MOA Plan Review for approval. |