Inspection #: 903255
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Current conditional electrical final extended until 7/1/2026 to resolve corrections below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/29/2026TransferCorrect Below* All units with dishwashers and disposals.Field installation has both appliances on the same circuit. Verify that engineer has submitted change order to MOA Plan Review.
5/29/2026TransferCorrect Below* 50A elevator circuits.1-line drawing shows (4) 50A elevator circuits supplied directly from MDP. Installation varies from 1-line drawing. Requires change order submitted to MOA Plan Review to show: 1. Coordination study between 200A feeder OCPD and 50A elevator circuit OCPDs. 2. 1-line changed to show 50A elevator circuits supplied from 200A elevator panels as installed. 3. Recalculated available fault current.
5/29/2026TransferCorrect Below* Available fault current table on drawings.Various panels show less than 10K available fault current. Table shows 22K equipment rating. Change table to allow 10K breakers and submit to MOA Plan Review for approval.
5/22/2026TransferCorrect Below* Roof top.2 out of 3 units not listed.
5/22/2026TransferCorrect Below* 3rd floor heat trace breakers.Require breaker locks.
5/22/2026TransferCorrect Below* Pool TV receptacle.Requires GFCI protection.
5/22/2026TransferCorrect Below* Pool area ceiling lights.Require GFCI protection. 680.22(B)(2). Breakers will have to meet any series rating requirements.
5/22/2026TransferCorrect Below* Pool area low voltage LED "waterfall" light.Low voltage lights within 5ft of water required to meet requirements of 680.22(B)(6) and supplied from power source meeting requirements of 680.23(A)(2). Low voltage class 2 wiring cannot be within gutter containing line voltage. Cut sheets and instructions required. UPDATE: RECEIVED "BRILLIANT WONDERS" POOL WATERFALL LIGHT PRODUCT INFORMATION. POWER SUPPLY USED DOES NOT APPEAR TO MEET NEC SECTION CITED ABOVE. ETL LISTING REP FOR THIS COMPANY NEEDS TO CONTACT INSPECTOR.
5/22/2026TransferCorrect Below* Pool pump room.EMT cannot be in corrosive environment.