| Date | Status | Code | Description | Ref | Location | Comments |
| 5/29/2026 | Transfer | Correct Below | * | | All units with dishwashers and disposals. | Field installation has both appliances on the same circuit. Verify that engineer has submitted change order to MOA Plan Review. |
| 5/29/2026 | Transfer | Correct Below | * | | 50A elevator circuits. | 1-line drawing shows (4) 50A elevator circuits supplied directly from MDP. Installation varies from 1-line drawing. Requires change order submitted to MOA Plan Review to show: 1. Coordination study between 200A feeder OCPD and 50A elevator circuit OCPDs. 2. 1-line changed to show 50A elevator circuits supplied from 200A elevator panels as installed. 3. Recalculated available fault current. |
| 5/29/2026 | Transfer | Correct Below | * | | Available fault current table on drawings. | Various panels show less than 10K available fault current. Table shows 22K equipment rating. Change table to allow 10K breakers and submit to MOA Plan Review for approval. |
| 5/22/2026 | Transfer | Correct Below | * | | Roof top. | 2 out of 3 units not listed. |
| 5/22/2026 | Transfer | Correct Below | * | | 3rd floor heat trace breakers. | Require breaker locks. |
| 5/22/2026 | Transfer | Correct Below | * | | Pool TV receptacle. | Requires GFCI protection. |
| 5/22/2026 | Transfer | Correct Below | * | | Pool area ceiling lights. | Require GFCI protection. 680.22(B)(2). Breakers will have to meet any series rating requirements. |
| 5/22/2026 | Transfer | Correct Below | * | | Pool area low voltage LED "waterfall" light. | Low voltage lights within 5ft of water required to meet requirements of 680.22(B)(6) and supplied from power source meeting requirements of 680.23(A)(2). Low voltage class 2 wiring cannot be within gutter containing line voltage. Cut sheets and instructions required. UPDATE: RECEIVED "BRILLIANT WONDERS" POOL WATERFALL LIGHT PRODUCT INFORMATION. POWER SUPPLY USED DOES NOT APPEAR TO MEET NEC SECTION CITED ABOVE. ETL LISTING REP FOR THIS COMPANY NEEDS TO CONTACT INSPECTOR. |
| 5/22/2026 | Transfer | Correct Below | * | | Pool pump room. | EMT cannot be in corrosive environment. |