Inspection #: 896142
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Final list of corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/22/2026TransferCorrect Below* Roof top.2 out of 3 units not listed.
5/22/2026TransferCorrect Below* 3rd floor heat trace breakers.Require breaker locks.
5/22/2026TransferCorrect Below* Pool TV receptacle.Requires GFCI protection.
5/22/2026TransferCorrect Below* Pool area ceiling lights.Require GFCI protection. 680.22(B)(2). Breakers will have to meet any series rating requirements.
5/22/2026TransferCorrect Below* Pool area low voltage LED "waterfall" light.Low voltage lights within 5ft of water required to meet requirements of 680.22(B)(6) and supplied from power source meeting requirements of 680.23(A)(2). Low voltage class 2 wiring cannot be within gutter containing line voltage. Cut sheets and instructions required.
5/22/2026TransferCorrect Below* Pool pump room.EMT cannot be in corrosive environment.
2/23/2026CorrectedCorrect Below* Pool pumps.208V, single phase pump motors require GFCI protection per 2017 NEC 680.21(C). Verify short circuit current rating as discussed.