| Date | Status | Code | Description | Ref | Location | Comments |
| 5/22/2026 | Transfer | Correct Below | * | | Roof top. | 2 out of 3 units not listed. |
| 5/22/2026 | Transfer | Correct Below | * | | 3rd floor heat trace breakers. | Require breaker locks. |
| 5/22/2026 | Transfer | Correct Below | * | | Pool TV receptacle. | Requires GFCI protection. |
| 5/22/2026 | Transfer | Correct Below | * | | Pool area ceiling lights. | Require GFCI protection. 680.22(B)(2). Breakers will have to meet any series rating requirements. |
| 5/22/2026 | Transfer | Correct Below | * | | Pool area low voltage LED "waterfall" light. | Low voltage lights within 5ft of water required to meet requirements of 680.22(B)(6) and supplied from power source meeting requirements of 680.23(A)(2). Low voltage class 2 wiring cannot be within gutter containing line voltage. Cut sheets and instructions required. |
| 5/22/2026 | Transfer | Correct Below | * | | Pool pump room. | EMT cannot be in corrosive environment. |
| 2/23/2026 | Corrected | Correct Below | * | | Pool pumps. | 208V, single phase pump motors require GFCI protection per 2017 NEC 680.21(C). Verify short circuit current rating as discussed. |