Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 895597
Inspection Type: Final Electrical
Inspector: M.Green
Result: Cancel
Comment: Cancelled by Coleman.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/23/2026TransferCorrect Below* Pool pumps.208V, single phase pump motors require GFCI protection per 2017 NEC 680.21(C). Verify short circuit current rating as discussed.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS