Click Here To View Another Inspection Inspection #: 892539 Inspection Type: Final Electrical Inspector: M.Green Result: Partial Comment: Conditional electrical final as described in inspection #886116 is extended until 6/1/2026. Note: Phase 3 ADA guest rooms received electrical final approval on 2/24/2026, inspection #892420. Phase 4 (pool and gazebo) not included in this conditional final. Inspection Corrections DateStatusCodeDescriptionRefLocationComments 2/23/2026TransferCorrect Below* Pool pumps.208V, single phase pump motors require GFCI protection per 2017 NEC 680.21(C). Verify short circuit current rating as discussed.