Inspection #: 892104
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Partial electrical final inspection of pool equipment room; not all equipment installed. Also, hotel is installing battery powered window shade operators in ADA rooms.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/23/2026TransferCorrect Below* Pool pumps.208V, single phase pump motors require GFCI protection per 2017 NEC 680.21(C). Verify short circuit current rating as discussed.