Click Here To View Another Inspection Inspection #: 892104 Inspection Type: Final Electrical Inspector: M.Green Result: Correction Comment: Partial electrical final inspection of pool equipment room; not all equipment installed. Also, hotel is installing battery powered window shade operators in ADA rooms. Inspection Corrections DateStatusCodeDescriptionRefLocationComments 2/23/2026TransferCorrect Below* Pool pumps.208V, single phase pump motors require GFCI protection per 2017 NEC 680.21(C). Verify short circuit current rating as discussed.