Inspection #: 889899
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Conditional electrical final - as described in inspection #886116 - extended until 4/1/2026.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/2/2026TransferCorrect Below* Somfy shade operator.In addition to the motor not being listed: 1. No apparent instructions showing a listed controller that might extend the listing to the shade motor. 2. No apparent integral overload protection. 3, No apparent instructions for selecting / installation of proper overload protection device. 4. No apparent instructions to provide overcurrent protection for the factory #18 cord.
2/2/2026TransferCorrect Below* Somfy shade operator.Not a listed product - only a UR mark as a component.