Inspection #: 886928
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Inspection to assess 120V shade operators for installation in ADA guest rooms.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/2/2026TransferCorrect Below* Somfy shade operator.In addition to the motor not being listed: 1. No apparent instructions showing a listed controller that might extend the listing to the shade motor. 2. No apparent integral overload protection. 3, No apparent instructions for selecting / installation of proper overload protection device. 4. No apparent instructions to provide overcurrent protection for the factory #18 cord.
2/2/2026TransferCorrect Below* Somfy shade operator.Not a listed product - only a UR mark as a component.
12/31/2025TransferCorrect Below* Engineered drawings available fault current table.Elevator panels show less than 10K available fault current. Table shows equipment rating of 22K. Many panels show less than 10K available fault current but 22K rated equipment. Various panel installations do not match the table requirement. Engineer needs to change table and submit to MOA Plan review.
12/31/2025TransferCorrect Below* (4) 50A elevator circuits.1-line drawing shows (4) 50A elevator circuits supplied directly from MDP. Installation varies from 1-line drawing. Change Order submitted to MOA Plan Review required to show: 1. Coordination study between 200A feeder and the 50A elevator circuits per NEC 620.62. 2. 1-line amended to show 50A elevator circuits supplied from 200A elevator panels as installed. 3. Recalculated available fault current.