Inspection #: 885981
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Progress electrical final covers: *Boiler / Mech Rooms. *Rooms 266 and 370. *Rooftop corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/22/2025TransferCorrect Below* Remaining rooftop corrections.1. Two, 50A AC units do not appear to have listing labels. 2. AC unit where roof penetration with LB violates 110.26 clearances: label to indicate reduced working clearances. 3. Disconnect labelling to include disconnect load and circuit source.
12/22/2025TransferCorrect Below* All Mech / Electric Room electrical panels.Will need to verify available fault current and series ratings / labelling if required.
12/22/2025TransferCorrect Below* 2nd floor Mech / Electrical Room HRU 201.1. Working clearance issues - wrap metal piping, etc. with non-conductive material. 2. Requires platform to provide flat standing space.
12/22/2025TransferCorrect Below* 1st floor exterior access Mech Room.1. (2) GFCIs not resetting. 2. At least (1) circuit not complete. 3. Unable to determine EM lights circuit.
12/22/2025TransferCorrect Below* 1st floor Boiler / Electrical Room.Panels H1 and H1A contain 10K rated breakers. Available fault current? Series Rating?
12/22/2025TransferCorrect Below* 1st floor Boiler / Electrical Room.Boilers OCPD reduced to 20A.
12/22/2025TransferCorrect Below* AHU 102 in 1st floor Boiler / Electrical Room.1. Non-conductive wrap on metal piping in working clearances. 2. Label to warn of reduced working clearances.
12/22/2025TransferCorrect Below* AHU in small mech room behind Housekeeping.Label shows MOP as 20.3A.
12/22/2025TransferCorrect Below* Various AHUs.Factory cord-like wiring method inside air handling spaces - working with ETL to determine conformance to listing standard.