| Date | Status | Code | Description | Ref | Location | Comments |
| 12/9/2025 | Transfer | Correct Below | * | | All guest rooms and guest suites. | 2017 NEC 210.12(C) requires AFCI protection for ALL branch circuits in hotel / motel guest rooms and suites. NOTE: this is a previous write-up. |
| 12/9/2025 | Transfer | Correct Below | * | | All units with dishwashers and disposals. | Contractor has put both appliances on one circuit. DW and disp. are less than 16A combined. Engineer needs to submit change order to MOA Plan Review for approval. |
| 12/9/2025 | Transfer | Correct Below | * | | Candlewood unit 371. | 1. Install bath lighted mirror. 2. DW / disp. receptacle not complete. |
| 12/9/2025 | Transfer | Correct Below | * | | Candlewood unit 370. (876661) | 1. Kitchen countertop receptacles dead both sides of cooktop. 2. DW / disp. receptacle not complete, needs add-a-depth. |
| 12/9/2025 | Transfer | Correct Below | * | | Candlewood unit 266 (879626). | 1. Install lighted mirror. 2. Install bath receptacle trim plate. 3. Panel requires source of supply labelling. 4. Panel requires panel schedule. |
| 12/9/2025 | Transfer | Correct Below | * | | Powered window shades. | "Fabtex" powered window shades: 1. Do not appear to have a listing mark. 2. Instructions show cord leads installed in walls. 400.12 prohibits cords installed in walls - clear evidence of unlisted equipment. Listed equipment required. |
| 12/9/2025 | Transfer | Correct Below | * | | All units with dishwashers. | Hole in cabinet is required to be large enough to pass attachment plug through. |