Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 884618
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: This reinspection covers inspection numbers 877725, 878215, 805607, 876661, 877317, 877315, 878530, 879625, 879626. Most corrections resolved. Some corrections remain. This inspection covers the hotel rooms contained in these reports, and specific adjacent common area issues. No EM lighting included.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/9/2025TransferCorrect Below* All guest rooms and guest suites. 2017 NEC 210.12(C) requires AFCI protection for ALL branch circuits in hotel / motel guest rooms and suites. NOTE: this is a previous write-up.
12/9/2025TransferCorrect Below* All units with dishwashers and disposals.Contractor has put both appliances on one circuit. DW and disp. are less than 16A combined. Engineer needs to submit change order to MOA Plan Review for approval.
12/9/2025TransferCorrect Below* Candlewood unit 371.1. Install bath lighted mirror. 2. DW / disp. receptacle not complete.
12/9/2025TransferCorrect Below* Candlewood unit 370. (876661)1. Kitchen countertop receptacles dead both sides of cooktop. 2. DW / disp. receptacle not complete, needs add-a-depth.
12/9/2025TransferCorrect Below* Candlewood unit 266 (879626).1. Install lighted mirror. 2. Install bath receptacle trim plate. 3. Panel requires source of supply labelling. 4. Panel requires panel schedule.
12/9/2025TransferCorrect Below* Powered window shades."Fabtex" powered window shades: 1. Do not appear to have a listing mark. 2. Instructions show cord leads installed in walls. 400.12 prohibits cords installed in walls - clear evidence of unlisted equipment. Listed equipment required.
12/9/2025TransferCorrect Below* All units with dishwashers.Hole in cabinet is required to be large enough to pass attachment plug through.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS