| Date | Status | Code | Description | Ref | Location | Comments |
| 12/5/2025 | Transfer | Correct Below | * | | Candlewood Suites 169, 170. | All kitchen countertop receptacles pulled out and hanging on wires for tile installation. |
| 12/5/2025 | Transfer | Correct Below | * | | Candlewood Suites with kitchens. | Original design shows (1) dedicated circuit for dishwasher and (1) circuit for disposal. Only (1) circuit being used for both. Engineer needs to submit Change Order to MOA Plan Review. |
| 12/5/2025 | Transfer | Correct Below | * | | Candlewood Suites with kitchens. | Dishwasher supply cord needs to be run through a hole in the cabinet that is of sufficient diameter to permit attachment plug pass-through. |
| 12/5/2025 | Transfer | Correct Below | * | | Holliday Inn kitchen. | 3-phase commercial dishwasher not on site. |