| Date | Status | Code | Description | Ref | Location | Comments |
| 11/26/2025 | Transfer | Correct Below | * | | 1st floor mechanical room Holiday and Candlewood | Did not inspect. |
| 11/26/2025 | Transfer | Correct Below | * | | Floors 2, 3, and 4 mechanical rooms (stacked only) | 1. Bond junction boxes.
2. Covers required on boxes.
3. AFCI protection required for all 120V outlets and devices in guest rooms per NEC 210.12(C).
4. Extended stay rooms require circuitry matching dwelling units per NEC 210.17.
5. No power at emergency lighting.
6. Some heat trace breakers do not have GFCI protection.
7. Heat trace breakers require breaker locks.
8. Available fault current at some subpanels exceeds AIC ratings. If series rated provide labeling per NEC 110.22.
9. Need to verify AIC ratings of breakers. |
| 11/25/2025 | Transfer | Correct Below | * | | Floor 1 electrical/boiler room. | 1. MDP available fault current exceeds AIC rating of equipment. Is equipment series rated?
2. Available fault current at some subpanels exceeds AIC ratings. If series rated provide labeling per NEC 110.22.
3. AFCI protection required for all 120V outlets and devices in guest rooms per NEC 210.12(C).
4. Extended stay rooms require circuitry matching dwelling units per NEC 210.17.
5. Panel M heat trace breakers require breaker locks and labeling on any pipes containing heat trace.
6. GFCI protection required for all pool pump motors and drinking fountains.
7. Branch circuit panels must contain unique descriptions for each circuit.
8. Unable to check emergency lighting.
9. Support flex conduit throughout per NEC 348.30.
|
| 11/19/2025 | Transfer | Correct Below | * | | Provide MOA stamped reviewed plans for inspection. Plans provided do not show all lighting. | |