Inspection #: 879627
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Candlewood Guest rooms 151-166 and adjacent hallways Requested by: Sloane Tuttle 907-917-7244 cb@g2const.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/30/2025TransferCorrect Below* 165, 166.General lighting not installed.
10/30/2025TransferCorrect Below* 162.Recept. below TV mis-wired.
10/30/2025TransferCorrect Below* 161.Trim plate missing - recept. by panel.
10/30/2025TransferCorrect Below* 159.1. Panel schedule not correct. 2. Shower recessed can not tight to sheetrock.
10/30/2025TransferCorrect Below* 157.1. DW / disp. receptacle not installed. 2. Kitchen light not installed. 3. LED bath mirror not installed. 4. Range hood circuit?
10/30/2025TransferCorrect Below* 155.Panel used for temp cords and cover not installed.
10/30/2025TransferCorrect Below* 153.Missing DW /disp. receptacle trim plate.
10/30/2025TransferCorrect Below* All.Panels require source of supply labelling as per earlier inspections.
10/30/2025TransferCorrect Below* Sink base cabinet.Hole for DW cord required to be large enough to pass the attachment plug as documented previously.
10/30/2025TransferCorrect Below* All.DW / disp. (2) circuits to (1) device yoke as previously documented.