Inspection #: 879626
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: 2nd floor Candlewood guest suites 265 - 276. Corrections below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/29/2025TransferCorrect Below* 275.1. Bath: complete lighted mirror and switch. 2. Main room north wall receptacles are dead.
10/29/2025TransferCorrect Below* 269, 270, 271, 272.Did not plug test due to large number of violations and incomplete work to include, but possibly not be limited to: Kitchen countertop receptacles hanging on wires, Kitchen peninsula pendants not hung, Cooktop hanging on MC, Other receptacle(s) missing.
10/29/2025TransferCorrect Below* 268.Circuit 20 labelled incorrectly as countertop receptacles.
10/29/2025TransferCorrect Below* 267.1. South wall rewired? No devices and trim. Sheetrock patching will be required. 2. Microwave circuit dead. Circuit not properly labelled.
10/29/2025TransferCorrect Below* 266 bathroom.1. Install lighted mirror. 2. Install receptacle trim plate.
10/29/2025TransferCorrect Below* All guest suites sink base cabinets.Hole for dishwasher cord is required to be large enough for attachment plug to pass through with all hoses, etc installed.
10/29/2025TransferCorrect Below* All DW / disp. split-wired receptacles.(2) circuits to (1) device yoke requires handle ties or 2-pole breaker.
10/29/2025TransferCorrect Below* All guest suite panels.Require source of supply labelling per NEC 408.4(B).