Inspection #: 879625
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: 2nd floor Candlewood guest suites 251-264 progress electrical final inspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/27/2025TransferCorrect Below* Guest suite 257.1. Panel schedule not correct. 2. Lighted bath mirror installation not complete.
10/27/2025TransferCorrect Below* All panels.Require source of supply labelling per 408.4(B).
10/27/2025TransferCorrect Below* All rooms dishwasher cords.Hole in cabinet required to be large enough to pass attachment plug through when hoses are installed.
10/27/2025TransferCorrect Below* All rooms DW / disp. receptacle.(2) circuits run to one device yoke requires handle ties or 2-pole breaker.