Inspection #: 877725
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Candlewood 4th floor guest suites 451 - 468. Corrections below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/17/2025TransferCorrect Below* Unit 468.Kitchen countertop AFCI / GFCI breaker is bad.
10/17/2025TransferCorrect Below* Split-wired dishwasher / disposal receptacles.Receptacles are supplied by (2), single pole AFCI / GFCI breakers. 2017 NEC 210.7 requires devices on the same yoke to have a means to simultaneously disconnect ungrounded conductors.
10/17/2025TransferCorrect Below* Unit panels.Post panel schedules.