Inspection #: 877317
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Progress electrical final inspection - 2nd floor Holliday guest rooms 210 - 212 and adjacent corridor. Did not check breakers in remote panels or EM lighting in corridor.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/23/2025TransferCorrect Below* Adjacent corridor.Receptacle, sconce lights not installed.
10/23/2025TransferCorrect Below* Guest room 209.Refrigerator receptacle and shelf receptacle above. Not GFCI protected like other rooms.
10/23/2025TransferCorrect Below* Guest room 204 powered curtains.Not a listed product. Power supply cords cannot be installed in walls. Same as previous comments on this issue.
10/23/2025TransferCorrect Below* Guest room 204 bath.Install lighted mirror.