Inspection #: 877315
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Progress electrical final inspection. 2nd floor Holliday guest rooms 213-226 (excludes 214 which had a do not enter sign) and adjacent corridor. NOTES: 1. Inspection does not cover panels and breakers feeding the units. 2. Corridor lighting / EM not tested.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/24/2025TransferCorrect Below* Adjacent corridor.At least (1) wall sconce not installed.
10/24/2025TransferCorrect Below* Any ADA rooms.Powered curtain listing and installation issues as documented before.
10/24/2025TransferCorrect Below* Rooms 216 and 225.Install lighted mirror.
10/14/2025TransferCorrect Below* ADA room 436. Also, likely in other ADA rooms."Fabtex" powered curtains: 1. Do not appear to have a listing mark. 2. Directions show cord leads from motors installed in walls. Cords installed in walls are a clear violation of several subsections of 400.12 Uses Not Permitted. This serves as further evidence that the product is not listed.