| Date | Status | Code | Description | Ref | Location | Comments |
| 12/18/2025 | Transfer | 01 | See inspection comments | | Disconnect labelling. | 1. Circuit load required.
2. Circuit source required.
3. Suitable for environment. |
| 12/18/2025 | Transfer | 01 | See inspection comments | | AC unit. | Working clearances violated by conduit stub-up with LB. Will require some sort of non-conductive material and warning label stating that working clearances are less than normal. |
| 12/18/2025 | Transfer | 01 | See inspection comments | | (1) mini-split AC compressor. | Fused disconnect 110.26 working clearances violated by gas lines. |
| 12/18/2025 | Transfer | 01 | See inspection comments | | (2) 50A rated AC units. | Do not appear to have listing marks. |
| 12/18/2025 | Transfer | 01 | See inspection comments | | Rooftop HRU 301 supply and exhaust fans stacked units. | 1. Upper unit does not have a ratings label.
2. Factory cord-like wiring method is an AWM. Will need to confirm plenum rating for acceptance.
3. Contractor needs to verify min / max OCPD ratings. One unit does not have a ratings label.
4. 300.22(D) provides rules for wiring inside plenums for environmental air. Liquid tight is not one of the wiring methods permitted. Metal flex is limited to 4ft.
5. Listing label stating "Recognized Component" may not be valid. |
| 3/20/2025 | Corrected | 01 | See inspection comments | | Guest Laundry 129. | Electrical rough not complete at washers and dryers. |