| Date | Status | Code | Description | Ref | Location | Comments |
| 4/8/2025 | Transfer | Correct service item below | * | | Temp power through MDP | Remove or isolate temp power supply that is passing through MDP. Temp Feeder may be required to be replaced with approved permanent feeder. Existing temp feed appears to be USE cable without equipment grounding conductor. |
| 4/8/2025 | Transfer | Correct service item below | * | | AFC and AIC ratings. | verify panels and other OCPD's have adequate AIC ratings based on engineer provided fault currents. |
| 4/8/2025 | Transfer | Correct service item below | * | | Service and panels, Change order documents. | Available fault current and labeling required. Could not locate fault currents on plans provided. If not already provided for plan review, submit fault currents and dates in change order. Also submit change order for revised one line of service configuration. Install does not match plans. Exterior OCPD service disconnect installed, onsite drawing details different install. |