Inspection #: 843080
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Lobby 171 walls. *Vestibule 172 walls. *Elevator Lobby 173 walls. *Office 174, 174.1, 174.2 walls. *Mech Room 175 walls and ceilings. *Restrooms 175.1 and 175.2. *Office 176 walls. *Office 176.1 walls and ceilings. *Hall C104 walls. Electrical rough approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/18/2024Transfer01See inspection comments Elevator shaft structural.Will not accommodate normal elevator controller installation at 4th floor shaft level. Verify elevator controller mounting before continuing.
12/18/2024Transfer01See inspection comments 1-line shows 50A elevator circuits originating in MDP.Will #8 CU be sufficient for voltage drop?
12/18/2024Transfer01See inspection comments 4th floor elevator lobby.Requires switch rough-in for top of shaft lighting.