Inspection #: 842845
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Holliday Inn 3rd floor guest rooms 321 - 329. Entry and bath framed-down ceilings electrical rough approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/18/2024Transfer01See inspection comments Elevator shaft structural.Will not accommodate normal elevator controller installation at 4th floor shaft level. Verify elevator controller mounting before continuing.
12/18/2024Transfer01See inspection comments 1-line shows 50A elevator circuits originating in MDP.Will #8 CU be sufficient for voltage drop?
12/18/2024Transfer01See inspection comments 4th floor elevator lobby.Requires switch rough-in for top of shaft lighting.