| Date | Status | Code | Description | Ref | Location | Comments |
| 12/18/2024 | Transfer | 01 | See inspection comments | | Elevator shaft structural. | Will not accommodate normal elevator controller installation at 4th floor shaft level. Verify elevator controller mounting before continuing. |
| 12/18/2024 | Transfer | 01 | See inspection comments | | 1-line shows 50A elevator circuits originating in MDP. | Will #8 CU be sufficient for voltage drop? |
| 12/18/2024 | Transfer | 01 | See inspection comments | | 4th floor elevator lobby. | Requires switch rough-in for top of shaft lighting. |