Inspection #: 836272
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: Elevator shafts (both) at pit and top of shaft. Electrical rough of MC stubs into pit area approved. Corrections are for 4th floor top of shaft area.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/18/2024Transfer01See inspection comments Elevator shaft structural.Will not accommodate normal elevator controller installation at 4th floor shaft level. Verify elevator controller mounting before continuing.
12/18/2024Transfer01See inspection comments 1-line shows 50A elevator circuits originating in MDP.Will #8 CU be sufficient for voltage drop?
12/18/2024Transfer01See inspection comments 4th floor elevator lobby.Requires switch rough-in for top of shaft lighting.