Inspection #: 806160
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: 4th floor Candlewood Suites, guest rooms 465-475. Electrical rough inspection excludes bathroom ceilings.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/12/2024Transfer01See inspection comments Guest suite receptacles.210.60(A) requires that guest rooms / suites with permanent provisions for cooking meet all the receptacle requirements of 210.52. 210.52 requires 6ft - 12ft spacing, etc.
6/12/2024Transfer01See inspection comments Various.Secure MC cables 1-1/4in minimum from nailing surface of stud.