| Date | Status | Code | Description | Ref | Location | Comments |
| 10/20/2025 | Transfer | Correct Below | * | | Unit 362 microwave receptacle. | Device required to be 20A rated. |
| 10/20/2025 | Transfer | Correct Below | * | | Units 360, 361 dishwasher / disposal receptacles. | Very loose. |
| 10/20/2025 | Transfer | Correct Below | * | | Unit 360 area outside bath. | Light fixture not installed. |
| 10/20/2025 | Transfer | Correct Below | * | | All split-wired dishwasher / disposal receptacles. | (2) circuits to one device yoke requires a 2-pole breaker or handle ties. |