Inspection #: 805607
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Progress electrical final inspection. 3rd floor Candlewood guest suites 359 - 366.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/20/2025TransferCorrect Below* Unit 362 microwave receptacle.Device required to be 20A rated.
10/20/2025TransferCorrect Below* Units 360, 361 dishwasher / disposal receptacles.Very loose.
10/20/2025TransferCorrect Below* Unit 360 area outside bath.Light fixture not installed.
10/20/2025TransferCorrect Below* All split-wired dishwasher / disposal receptacles.(2) circuits to one device yoke requires a 2-pole breaker or handle ties.