Click Here To View Another Inspection Inspection #: 680694 Inspection Type: Undergound Electrical Inspector: M.Green Result: Partial Comment: PVC underground, northwest 1/4 of site approved EXCEPT: *At light pole bases (last 5ft of conduit into bases required to be GRC). *North side of site along W48th. *At locations where conduit is to sleeve through West side retaining wall along C Street. *Home runs where conduits enter building footprint. Inspection Corrections DateStatusCodeDescriptionRefLocationComments