Permit Type: Commercial Building Permit - None BldgAlter
Address: W 330 DIMOND BLVD Anchorage
Location:
Work Description: Work Descr: pharmacy expansion / remodel, Remarks: mgm
Status: Closed
Project Name: COSTCO
Review Type: Fire
Result: Approved
Result Date: 8/23/2005 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): SPRINKLER SYSTEM: At final inspection provide a copy of the current annual service report showing no deficiencies to the system. Provide an AFD Install Certificate from the sprinkler contrctor for any changes to the system. Obtain separate permit if required. C(2): FIRE EXTINGUISHER: Add or relocate as required per IFC 906. Inspector will field verify. a minimum 2a10BC extinguisher shall be located within 75 ft travel distance from any point within the building.