Address: 7701 DEBARR RD Anchorage
Location:
Work Description: REPLACE EXISTING 500 GALLON ABOVE GROUND FUEL OIL TANK WITH NEW 500 GALLON FUEL OIL TANK WITH FUEL PIPING TO EMERGENCY GENERATOR- CCK 
A Flood Hazard Permit has been sent to the applicant for signature and must be received prior to Final CO.
Status: Issued
Project Name:
Review Type: Flood
Result: Correction
Result Date: 11/26/2024 5:58:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

The Base Flood Elevation is 243.8 Feet, Mean Sea Level 1972, Vertical Datum.
Provide the lowest grade elevation adjacent to the fuel tank slab.
Provide top of slab elevation. The slab elevation must be 1.0 foot above the BFE.  The slab elevation must be 244.8 feet msl 1972 or higher.
Will there be asphalt pavement up to the edge of the support slab? 
If you don't want to elevate the fuel tank support slab, lateral load and buoyancy calculations may be required for flood flow.

An as-built for the site elevations will be required to close this permit.