Permit Number: C21-1711
Permit Type: Commercial Building Permit - None BldgAdd
Address: W 330 DIMOND BLVD Anchorage
Location:
Work Description: EPLANS - 2106 SF - VB CONSTRUCTION - CONSTRUCTION  OF NEW MEZZANINE FOR ADDITIONAL BREAKROOM OVER EXISTING EMPLOYEE LOUNGE - ADB
MG2 CORPORATION PAID $1720.68 FOR PLAN REVIEW FEES - ADB 8/10/21
COSTCO PAID REMAINING BALANCE 11/17/21 - ADB
ELECTRONIC FOLDER - SEE ATTACHMENTS
Status: Closed
Project Name: EPLANS - COSTCO
Review Type: Structural
Result: Correction
Result Date: 8/26/2021 9:41:52 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Note: Comment information provided here is automatically generated and provided for reference only. Please view comment markups directly in ePlans for full context. ePlans logins are available by contacting the permit Review Coordinator.


10
1
Structural
Grant Gephardt
8/24/21 12:09 PM
Changemark
STRUCT-CALCS-001
Site Coefficient Fa is required to be 1.2 if Site Class D is assumed per ASCE 7-16 11.4.3-4. Please update calculations and design as required.
STRUCTURAL CALCULATION.pdf
 
Unresolved
11
1
Structural
Grant Gephardt
8/24/21 12:18 PM
Changemark
STRUCT-S0.1-001
Unlikely to affect this project, but this location is in 145 mph Zone II per the MOA's Wind Speed Map: https://www.muni.org/departments/ocpd/development-services/permits-inspections/documents/wind_bowl_sq.pdf. Please update criteria.
S0.1.pdf
 
Unresolved
12
1
Structural
Grant Gephardt
8/25/21 12:37 PM
Changemark
STRUCT-S1.1-001
This appears to be an independent structure. How is seismic separation from the existing building elements such as columns and walls achieved? What is the required separation? Please clarify the intent. [Reference: ASCE 7-16 12.12.3]
S1.1.pdf
 
Unresolved
13
1
Structural
Grant Gephardt
8/25/21 4:43 PM
Changemark
STRUCT-S0.1-002
Where is the yield strength for light gauge steel floor members specified? Please provide or indicate where this information is already called out.
S0.1.pdf
 
Unresolved
14
1
Structural
Grant Gephardt
8/26/21 9:16 AM
Changemark
STRUCT-CALCS-002
Please provide the analysis for the Titen anchors for these holddowns per ER-124 Sec. 4.1.4.
STRUCTURAL CALCULATION.pdf
 
Unresolved
15
1
Structural
Grant Gephardt
8/26/21 9:25 AM
Comment
Please provide a letter from the Owner indicating who they will be hiring to provide the special inspections for this project. The special inspectors must be licensed by the Municipality of Anchorage in the types of inspections to be performed. [Reference: IBC 2018 § 1704.2, AMC § 23.15.1703.7]
  
Unresolved
16
1
Structural
Grant Gephardt
8/26/21 9:37 AM
Changemark
STRUCT-S1.1-002
Is 1600S162-54 an available shape? It's not listed in the SSMA catalog. Please verify.
S1.1.pdf
 
Unresolved