Permit Number:
C21-1711
Permit Type:
Commercial Building Permit - None BldgAdd
Address:
W 330 DIMOND BLVD Anchorage
Location:
Work Description:
EPLANS - 2106 SF - VB CONSTRUCTION - CONSTRUCTION OF NEW MEZZANINE FOR ADDITIONAL BREAKROOM OVER EXISTING EMPLOYEE LOUNGE - ADB
MG2 CORPORATION PAID $1720.68 FOR PLAN REVIEW FEES - ADB 8/10/21
COSTCO PAID REMAINING BALANCE 11/17/21 - ADB
ELECTRONIC FOLDER - SEE ATTACHMENTS
Status:
Closed
Project Name:
EPLANS - COSTCO
Review Type:
Electrical
Result:
Approved
Result Date:
8/12/2021 3:12:00 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
Electrical Plan Review Status:
The electrical plans are reviewed and approved.
----------------------------------------------------------------------------------------------
THE FOLLOWING COMMENTS ARE ADDRESSED ON THE E-PLANS
CIRCUIT DIRECTORY OR CIRCUIT INDENATION ON FLOOR PLAN & PANEL SCHEDUL: Panel schedule and floor plan do not have same circuit identifications. For example: many circuits in panel P18 are named vending machine, and counter recept. These circuits should be clearly identified. No two circuits should have the same identification/names. Refer to NEC
EXISTING SERVICE LOAD CALCULATIONS:
There are additional panel added to the MDP section. The plan have no calculations for the feeder loads for the existing panels as required by NEC Section 220.87. Please address.
Comment 408.4 for circuit identifications.