Permit Number:
C21-1711
Permit Type:
Commercial Building Permit - None BldgAdd
Address:
W 330 DIMOND BLVD Anchorage
Location:
Work Description:
EPLANS - 2106 SF - VB CONSTRUCTION - CONSTRUCTION OF NEW MEZZANINE FOR ADDITIONAL BREAKROOM OVER EXISTING EMPLOYEE LOUNGE - ADB
MG2 CORPORATION PAID $1720.68 FOR PLAN REVIEW FEES - ADB 8/10/21
COSTCO PAID REMAINING BALANCE 11/17/21 - ADB
ELECTRONIC FOLDER - SEE ATTACHMENTS
Status:
Closed
Project Name:
EPLANS - COSTCO
Review Type:
Architectural
Result:
Correction
Result Date:
8/12/2021 12:43:00 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
1
1
Fire
Mark Panilo
8/12/21 11:36 AM
Changemark
HANDRAIL EXTENSIONS
Please clarify the handrail extensions for the new flight of stairs from the existing landing to the new mezzanine landing. The section appears to show the riser in the same plane as the existing wall, which will not provide for any extension into the existing landing without creating an obstacle. Reference: IFC Section 1014.6
A502.1.pdf
Unresolved
2
1
Fire
Mark Panilo
8/12/21 11:36 AM
Changemark
RISER HEIGHT
Please clarify the number of risers for the stairs. The elevation difference shown over the number of risers exceeds the maximum riser height. Reference: IFC Section 1011.5.2
A502.1.pdf
Unresolved
3
1
Fire
Mark Panilo
8/12/21 11:38 AM
Library Comment
Please note on the plans the location(s) and rating(s) of the fire extinguisher(s) serving each level. Fire extinguishers shall be located appropriate for the rating, travel distance, and occupancy hazard. Ref: IFC Section 906.3
Unresolved
4
1
Architectural
Don Crafts
8/12/21 12:26 PM
Changemark
ARCH #01
Respond to fire comment regarding the number of stair risers. It appears that 24 risers would be required here.
A502.1.pdf
Unresolved
5
1
Architectural
Don Crafts
8/12/21 12:26 PM
Changemark
ARCH #02
Respond to Fire Plan Review comment regarding the bottom of the stairway handrail extensions. It appears that the stairway would have to be shifted approximately one foot toward the K column line to accommodate this requirement that you presently show in detail
A502.1.pdf
Unresolved
6
1
Architectural
Don Crafts
8/12/21 12:40 PM
Changemark
ARCH #03
Did you intend this to be 17/G101? Or is 2/G101 missing?
A502.1.pdf
Unresolved
7
1
Architectural
Don Crafts
8/12/21 12:40 PM
Changemark
ARCH #04
Did you intend this to be 17/G101? Or is 2/G101 missing?
A502.1.pdf
Unresolved