Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C18-2139
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 330 DIMOND BLVD Anchorage
Location:
Work Description: REPLACE EXISTING STORAGE RACKS WITH NEW STORAGE RACKS - MJD
Status: Expired
Project Name: COSTCO STORAGE RACKS
Review Type: Fire
Result: Approved
Result Date: 3/29/2019 3:03:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Provide fire extinguisher conforming to 75ft travel distances throughout the building; several areas do not meet TD. (IFC 906.3)

2_Resolved
Detail a K Class extinguisher in food service area per IFC 904.11.5

3_Resolved
Provide for exit sign and emergency egress lighting IF new rack configuration differs from existing.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter