Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C18-2329
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 330 DIMOND BLVD Anchorage
Location:
Work Description: TENANT IMPROVEMENT TO REPLACE EXISTING DOOR WITH A ROLL UP SERVICE DOOR IN THE EXISTING TIRE CENTER IN THE EXISTING ANCHORAGE COSTCO.  AE
Status: Expired
Project Name: COSTCO TIRE CENTER DOOR
Review Type: Structural
Result: Approved
Result Date: 2/11/2019 11:18:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Structural Comments

Reviewed by: Ralph Jordan                                                          Permit#: C18-2329

Phone:343-8371                                                                            
Fax:     249-7775                                                                              

Email: ralph.jordan@anchorageak.gov
Permit Manager: Andrew Earp    

Phone: 343-8338
Email:  andrew.earp@anchorageak.gov
Project: Costco
Warehouse #10 Tire Center Opening

Review #2

___________________________________________________________________________________  

Advisory Comment: Reviewed under IBC 2012 and
local amendments. This review does not permit the violation of the building
codes or any governmental regulation.


 Structural Comments:

Comments from Review #1 resolved. No additional comments.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter