Permit Number: C18-2329
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 330 DIMOND BLVD Anchorage
Location:
Work Description: TENANT IMPROVEMENT TO REPLACE EXISTING DOOR WITH A ROLL UP SERVICE DOOR IN THE EXISTING TIRE CENTER IN THE EXISTING ANCHORAGE COSTCO.  AE
Status: Expired
Project Name: COSTCO TIRE CENTER DOOR
Review Type: Structural
Result: Correction
Result Date: 12/11/2018 3:39:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Structural Comments

Reviewed by: Ralph Jordan                                                           Permit#: C18-2329

Phone: 343-8371                                                                             Date12-11-18
Fax:     249-7775                                                                              

Email:  ralph.jordan@anchorageak.gov
Permit Manager: Andrew Earp    

Phone: 343-8338
Email:  andrew.earp@anchorageak.gov
Project: Costco
Warehouse #10 Tire Center Opening

Review #1

___________________________________________________________________________________  

Advisory Comment: Reviewed under IBC 2012 and
local amendments. This review does not permit the violation of the building
codes or any governmental regulation.


 Structural Comments:

  1. Please
    provide a letter from the special inspection agency doing the special
    inspections for welding and post installed anchors as listed on Sheet S1.1.

  2. Please
    verify strong backs to be 6x6x1/4 per S1.1 and not 7x7x1/4 as called out on
    Sheet A504.

     

Please address all comments and provide submittals as necessary to the permit manager.

Further review may be required.