Permit Number:
X16-1519
Permit Type:
Commercial Building Permit - ChangeOrdr BldgCombo
Address:
7701 DEBARR RD Anchorage
Location:
Work Description:
Replacement of existing RTU's 1 thru 5 with new curbs provided for structural deferred with minor interior duct work connection to include electric - BWP
Status:
Closed
Project Name:
Change Order of Bldg App C15-1739
Review Type:
Structural
Result:
Correction
Result Date:
7/20/2016 9:28:15 AM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
The calculations do not address wind loading on the proposed units. Given the size of the units, wind loads potentially control the design of the anchoring, especially in consideration of the rooftop equipment factor per ASCE 7. Please provide updated calculations including wind load evaluation, and revised anchorage details as necessary.
Reference: IBC Section 1605.1, 1609.1.1; ASCE 7 Section 6.5.15
7/20/16 - Resolved. Wind calculations provided. Additional comments issued. MMP
2
_
Refer to Calculations Pg. 4. The determination of the wind load does not appear to include the rooftop equipment factor per ASCE 7. Given the size of the building, an additional factor of 1.9 is required.
Reference: IBC Section 1609.1.1; ASCE 7 Section 6.5.15.1
3
_
Refer to Calculations Pg. 4. The determination of the overturning resistance due to dead load does not include applicable load factors. Please revise calculations accordingly.
Reference: IBC Section 1605.2