Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
X16-1519
Permit Type:
Commercial Building Permit - ChangeOrdr BldgCombo
Address:
7701 DEBARR RD Anchorage
Location:
Work Description:
Replacement of existing RTU's 1 thru 5 with new curbs provided for structural deferred with minor interior duct work connection to include electric - BWP
Status:
Closed
Project Name:
Change Order of Bldg App C15-1739
Review Type:
Structural
Result:
Correction
Result Date:
6/29/2016 2:16:44 PM
Comments:
Code Section
Review Comment
Status
1
_
The calculations do not address wind loading on the proposed units. Given the size of the units, wind loads potentially control the design of the anchoring, especially in consideration of the rooftop equipment factor per ASCE 7. Please provide updated calculations including wind load evaluation, and revised anchorage details as necessary.
Reference: IBC Section 1605.1, 1609.1.1; ASCE 7 Section 6.5.15
Advisory Information:
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501