Permit Number: F15-1441
Permit Type: Commercial Trade Permit - Alteration Fire
Address: 7701 DEBARR RD Anchorage
Location:
Work Description:

18 FIRE ALARM DEVICES-GJS

CHILD OF C15-1739

Status: Closed
Project Name: FRED MEYERS C15-1739
Review Type: Fire System
Result: Approved
Result Date: 10/22/2015 11:23:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Municipality of Anchorage

 

Building Safety Division

 

Fire System Comments

 

Reviewed by: Mark Warren                                                         Permit #: F15-1441

Phone: 267-4992                                                                        Date: 10/21/2015, approved on 10/22/2015

Fax: 249-7393

Email: warrenmj@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Debarr Fred Myer                  

Review Number: 361698

____________________________________________________________________________________

 

PERMIT STATUS: Corrections

 

1)       The design professional is not on the State of Alaska permit list for design of fire alarm.

Resolved  

2)       The area within the employee pharmacy work area does not have visual notification.

Resolved.

3)       The candela ratings in the bathrooms are not enough for the area.

Outside scope of work.

4)       The horn\strobes in Liquor and in the electric room either need to be centered to the room or upgraded to a higher candela. Outside the scope of work.

 

 