Permit Number: E15-1741
Permit Type: Commercial Trade Permit - Alteration Electrical
Address: W 330 DIMOND BLVD Anchorage
Location:
Work Description: Installation of 2 circuits and 1 50A subpanel - BWP
Status: Closed
Project Name: COSTCO
Review Type: Electrical
Result: Correction
Result Date: 7/1/2015 11:28:56 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Electrical Comments

 

Reviewed by: David Abuobaid                                                   Permit #: E15-741

Phone: 343-8333                                                                        Date: 7/1/2015

Fax:     249-7775                                                                      

Email:  AbuobaidDH@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email:  Parkerrw@muni.org

Project: Castco (Fax #: 479-927-4817)

____________________________________________________________________________________  

 

REQUIREMENT OF ELECTRICAL SCOPE OF WORK:

The scope of work is to sub-feed new 100 Amp panel and two circuits for the three computers.

Provide 100% designed engineered drawing by a registered professional electrical engineer of the State of Alaska. The design shall include wiring method, home run wiring with type, size of wires and conduits, over-current protection, accessibility to over-current protection, existing service load calculations, panel schedules with connected and demand loads and one-line diagram.