Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: M15-1116
Permit Type: Commercial Trade Permit - Alteration Mechanical
Address: W 330 DIMOND BLVD Anchorage
Location:
Work Description:

REMOVE AND REPLACE SALES FLOOR COOLER IN SAME LOCATION-GJS

PERMIT FEE TO BE PAID UPON ISSUANCE-GJS

Status: Closed
Project Name: COSTCO DIMOND
Review Type: Electrical
Result: Approved
Result Date: 6/10/2015 11:27:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved

Electrical Comments

 

Reviewed by: David Abuobaid                                                   Permit #: M15-11116

Phone: 343-8333                                    /                                   Date: 6/10/2015

Fax:     249-7775

Email:  AbuobaidDH@muni.org

Permit  Manager: Tony Barganier

Phone: 343-8339

Email:  BarganierWA@muni.org

Project: COSTCO (Fax#: no fax provided)

 

1.  Electrical Status: Correction required 6/10/2015.



2_Resolved

2. The following comments based on the 2011 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local regulations.



3_Resolved

3. CIRCUIT DIRECTORY OR CIRCUIT INDENTIFICATION ON FLOOR PLAN & PANEL SCHEDULES:

Sheet E-2 (Floor Plans and Panel Schedules). There are generic names for circuit breakers. Panel schedule P2 and floor plans should have same name / identification. For example; panel schedules have many circuits POS Cooler Dr heater, POS FZR S Door Heater, and many other circuits have same names. Note that circuits should be identified clearly on floor plans to match panel schedules and not two circuits should have same name / identifications. Refer to NEC 408.4.



4_Resolved

4. AVAILABLE FAULT CURRENT:

Sheet E-2 (Field Marking - Available Fault Current). Verify that the available fault current is calculated and marked on the service equipment. NEC section 110.24 requires that service equipment be legibly marked in the field with maximum available fault current. The field markings shall include the date the fault current calculation was performed and be of sufficient durability to withstand the environment involved.



5_Resolved

5.  AMPERAGE INTERRUPTING AMPACITY:

Sheet E-2 (Line Diagram and Panel Schedule). Panel schedules H5 and P4 show no AIC rating. Provide detail AIC calculation if any panel AIC rating is exceeds 10,000A.



6_Resolved

6.  When the above comments have been addressed, please update the electrical plans at the MOA Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature. 






Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter