Permit Number: M15-1116
Permit Type: Commercial Trade Permit - Alteration Mechanical
Address: W 330 DIMOND BLVD Anchorage
Location:
Work Description:

REMOVE AND REPLACE SALES FLOOR COOLER IN SAME LOCATION-GJS

PERMIT FEE TO BE PAID UPON ISSUANCE-GJS

Status: Closed
Project Name: COSTCO DIMOND
Review Type: Structural
Result: Correction
Result Date: 3/9/2015 12:56:35 PM

Comments:

 Code SectionReview CommentStatus
1_

COMPRESSOR

Reference the compressor replacement design. Please provide design of the new compressor’s anchorage for seismic forces per ASCE 7-05, Chapter 13. This item can be deferred.



2_

MOMENT FRAME

Reference detail 12 on sheet 141925-D of the drawings. Single sided fillets or partial penetration welds are not permitted to be used to resist tension due to seismic forces per AISC 341-05 section 11.2a(3). These connections must be designed for an R=1 (maximum force that can be delivered by the system) or 1.1*Ry*Mp of the column or beam whichever is smallest. Reference AISC 341-05 section 11.2a.



3_

ANCHORAGE AT FRAMES

The anchorage at frames must meet ACI 318-05 Appendix D including the ductile or non ductile yielding requirements of sections D3.3.4 through D3.3.6.



4_

USE OF ANTHONY DOOR FRAMES

Reference the design. The design calls for the use of Anthony Door Frames for lateral resistance in the long direction. Please provide substantiating data showing these frames are acceptable. The test data provided appears to cover a specific height, and can not be readily adapted to the much taller height on this project. It’s possible another system is being used since there appears to be HSS 4X4 seismic columns called out in the details, but this isn’t clear from the design. Please indicate the frames on the drawings including all material specifications, connections, etc. Reference AAC section 23.10.104.8 and IBC section 1703.4.



5_

STATEMENT OF SPECIAL INSPECTIONS

Please provide a statement of special inspections as required by IBC section 1705. The statement of special inspections must include both the type and frequency of inspection.



6_

SPECIAL INSPECTORS

Please provide a letter from the Owner indicating who they will be hiring to provide the special inspections for this project. The special inspectors must be licensed by MOA in the types of inspections to be performed. Reference IBC section 1703.1.






Advisory Information:

Reviewed by: Bolen, Wayne A.                                                  Permit #: C15-1020

Phone: 343-8072                                                                        Date: 3/9/2015

Fax: 249-7393

Email: BolenWA@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Costco #10 Cooler Box

Review Number: 347274

____________________________________________________________________________________

 

PERMIT STATUS

3/9/2015 – Review complete. Comments issued.

 

Advisory Comment (no response required):  This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.

 

All submittals should be sent to the permit manager.

 