Reviewed by: Bolen, Wayne A. Permit #: C14-1693
Phone: 343-8072 Date: 8/22/2014
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tommy Cornell
Phone: 343-8181
Email: BarganierTA@muni.org
Project: Dimond Costco Diesel Tank Upgrade
Review Number: 336700
____________________________________________________________________________________
PERMIT STATUS
8/22/2014 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. Please provide calculations showing the deadman has sufficient capacity to transfer it's resisting weight. This weight is just the total buoyancy force - (the resisting weigth - the soil over grade beam weight - the grade beam weight). Reference IBC section 1604.2. Please remember that buoyancy force is an H force like lateral earth pressure and must be factored by 1.6. See "Notations" under IBC section 1602.1.
Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.